Heyco Liquid Tight Cord Grips EMC Brass CordgripsMetric Hubs
EMC Nickel Plated Brass

Material: Nickel-Plated Brass with TPE Sealing Gland

Certifications:

File E51579

Temperature Rating: -40°C to 100°C (-40°F to 212°F)

Ingress Protection Rating: IP 68, IP 69K

 
  • Ideal for applications where Electromagnetic Compatibility (EMC) is needed.
  • Nickel-plated finish over brass provides excellent corrosion resistance and durability.
  • Excellent 360° shield contact with contact sleeve due to braided shield which runs into the gland.
  • Combination of the sealing insert and the contact socket guarantees a constant contact quality with minimal transfer impedance.
  • Inner cable protection.
  • Long metric thread for use in standard or thick panels.
  • Multiple sizes for flexible cord diameters ranging from .10" to .98" (2,5 mm to 25,0 mm).
  • For use in clearance or threaded holes.
  • Cordgrips are made of nickel plated brass and the gland is made of TPE.
  • EMC Locknuts available.
Heyco®-Tite EMC Brass Liquid Tight Cordgrips
EMC Nickel-Plated Brass with Contact Sleeve, Metric Hubs
The Ultimate in Liquid Tight Strain Relief Protection
Cable Diameter Range Part
Number
Thread
Size
Part Dimensions
Min.- Max. Min.- Max. A
Clearance Hole Dia.
B
Max. Overall Length
C
Thread Length
D
Wrenching Flats
in. mm. in. mm. in. mm. in. mm. in. mm.
.10 - .14 2,5 - 3,5 4613 M8 x 1,25   .33   8,4   .94 24,0 .39 10,0   .43 11,0
.12 - .16 3,0 - 4,0 4614
.12 - .16 3,0 - 4,0 4615 M10 x 1,5   .41 10,4   .98 25,0 .39 10,0   .51 13,0
.16 - .24 4,0 - 6,0 4616
.18 - .24 4,5 - 6,0 4618 M12 x 1,5   .50 12,7 1.06 27,0 .39 10,0   .59 15,0
.24 - .30 6,0 - 7,5 4619
.24 - .32 6,0 - 8,0 4608 M16 x 1,5   .64 16,5   .98 25,0 .20   5,0   .71 18,0
.32 - .39   8,0 - 10,0 4607 1.06 27,0
.24 - .32 6,0 - 8,0 4622 M16 x 1,5   .64 16,5 1.18 30,0 .39 10,0   .71 18,0
.32 - .39   8,0 - 10,0 4623 1.26 32,0
.32 - .43   8,0 - 11,0 4625 M20 x 1,5   .80 20,5 1.22 31,0 .39 10,0   .94 24,0
.43 - .55 11,0 - 14,0 4626 1.30 33,0
.51 - .63 13,0 - 16,0 4628 M25 x 1,5 1.00 25,4 1.41 36,0 .43 11,0 1.18 30,0
.63 - .75 16,0 - 19,0 4629 1.53 39,0
.71 - .83 18,0 - 21,0 4631 M32 x 1,5 1.27 32,3 1.65 42,0 .51 13,0 1.42 36,0
.83 - .98 21,0 - 25,0 4632
Hit Temperature *
.24 - .32 6,0 - 8,0 4609 M16 x 1,5   .64 16,5   .99 25,1 .20 5,1   .71 18,0
* Special sealing gland rated to 200°C (392°F)
  For additional sizes see EMC Nickel-Plated Brass Cordgrips - PG Hubs
 

Heyco® Metal Locknuts
EMC Nickel Plated Brass, Metric Threads
Thread Size Part
Number
Description Part Dimensions
A
Thickness
B
Wrenching Flats
in. mm. in. mm.
M8 x 1,25 4681 EMC LN M8   .13 3,3   .43 11,0
M10 x 1,5 4682 EMC LN M10   .51 13,0
M12 x 1,5 4683 EMC LN M12 .14 3,5   .59 15,0
M16 x 1,5 4684 EMC LN M16   .75 19,0
M20 x 1,5 4685 EMC LN M20 .16 4,0   .94 24,0
M25 x 1,5 4686 EMC LN M25 1.18 30,0
M32 x 1,5 4687 EMC LN M32 .20 5,0 1.42 36,0
EMC Nickel Plated Brass Locknut